M8013 Mitsubishi Plc Apr 2026

----[ M8013 ]----[PLS M10]----[MOV D100 D200] // Log every second Do not use M8013 for critical timing or safety functions.

It is neither. The "M" stands for . It exists only inside the PLC’s memory. You cannot wire a physical switch to it, and it cannot drive a real load directly. You must use its contact to trigger an output coil (Y0, Y1, etc.). M8013 vs. Other Special Relays | Relay | Pulse Rate | Common Use | | :--- | :--- | :--- | | M8011 | 10ms (100 Hz) | High-speed flashing, test pulses | | M8012 | 100ms (10 Hz) | Fast blinking, short delays | | M8013 | 1 second (0.5 Hz) | Human-scale timing, indicators | | M8014 | 1 minute (0.0167 Hz) | Long-interval polling, hour meters | Final Verdict: Should You Use M8013? Absolutely. M8013 is one of those elegant, simple tools that makes PLC programming faster and more readable. Instead of writing a 5-rung timer oscillator, you write one contact. m8013 mitsubishi plc

----[ M8013 ]--------------( M100 ) // Heartbeat bit On the HMI, animate an invisible shape or text color based on M100. If the blinking stops, the operator knows the PLC is in STOP mode or has faulted. Mechanical pushbuttons and limit switches bounce for 5–20ms. A common trick: sample the input every 500ms using M8013. ----[ M8013 ]----[PLS M10]----[MOV D100 D200] // Log